Article number
Source/sink input
Input characteristic curve in accordance with IEC
61131, type 3
Digital input functions, parameterizable
Freely usable digital input
Probe
Digital input with time stamp
Counter
Digital input with oversampling
Input voltage
Type of input voltage
Rated value (DC)
for signal "0"
for signal "1"
permissible voltage at input, min.
permissible voltage at input, max.
Input current
for signal "1", typ.
Input delay (for rated value of input voltage)
Minimum pulse width for program reactions
for standard inputs
parameterizable
with "0" to "1", typ.
with "1" to "0", typ.
for interrupt inputs
parameterizable
for technological functions
parameterizable
with "0" to "1", typ.
with "1" to "0", typ.
Cable length
shielded, max.
unshielded, max.
Digital outputs
Type of digital output
integrated channels (DO)
Current-sinking
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC
6ES7615-4DF10-0AB0
P-reading
Yes
 
Yes; Max. 20 (X122/X132) + max. 8 (X142)
Yes; Max. 8 (X122/X132) + max. 8 (X142)
Yes; Max. 8 (X142); e.g. for probes
Yes; Max. 8 (X142); event/cycle duration measurement
Yes; Max. 8 (X142); 32-fold oversampling
 
DC
24 V
-3 to +5V
+15 to +30 V
-30 V
30 V
 
4 mA
 
5 µs for X122/X132/X142 (DI/DQ as DI; for X142 with filter setting 1
µs)
 
No; For X122/X132
For X122/X132: 10 µs (DI) / 5 µs (DI/DQ as DI)
For X122/X132: 30 µs (DI) / 5 µs (DI/DQ as DI)
 
Yes; identical to those for technological functions
 
Yes; For X142, additionally adjustable input filter: 1 µs / 125 µs
5 µs; For X142; HW delay
5 µs; For X142; HW delay
 
30 m; For technological functions: Shielding of the DI recommended
depending on the requirements
30 m
 
Transistor
16; max. depending on parameterization
Yes; With High Speed output
Technical specifications