Commissioning
11.4 Operating and system states
Transition
Description
The primary CPU is in the RUN operating state. The redundant system switches
from the RUN-Solo system state to the SYNCUP system state if:
You set the backup CPU to RUN via the PG/PC, the display or the RH_CTRL
instruction (Mode 7) and the mode selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN)
and
the SYNCUP system state is not disabled by the RH_CTRL instruction.
Operating state
RUN → RUN-Syncup
transitions
The primary CPU switches from the RUN operating state to the RUN-Syncup
operating state if:
You set the backup CPU to RUN via the PG/PC or the display and the mode
selector is set to RUN
or
You switch the mode selector on the backup CPU from STOP to RUN.
or
You POWER ON the backup CPU (mode selector to RUN).
STOP → SYNCUP
The backup CPU switches from the STOP operating state to the SYNCUP operat­
ing state.
SYNCUP → RUN-Redundant, RUN-Syncup → RUN-Redundant
Transition
Description
System state trans­
SYNCUP → RUN-Redundant
ition
The redundant system switches from SYNCUP to the RUN-Redundant system
state if SYNCUP has successfully run.
In the RUN-Redundant system state, the two CPUs execute the user program
synchronously.
Note: A temporary increase in the cycle time can occur upon a system
state transition SYNCUP → RUN-Redundant. Configure a sufficiently long
maximum cycle time for the CPUs.
Operating state
RUN-Syncup → RUN-Redundant
transitions
The primary CPU switches from the RUN-Syncup operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
SYNCUP → RUN-Redundant
The backup CPU switches from the SYNCUP operating state to the RUN-
Redundant operating state if SYNCUP has successfully run.
286
Effects
See section SYNCUP sys­
tem state (Page 270)
Effects
This system state trans­
ition does not have any
effect on data.
Communication connec­
tions (HMI, PG/PC) on
the backup CPU become
available.
Both CPUs process the
user program synchron­
ously.
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD