Function Revision History; Verifying The Signals And Settings; Measuring The Operate Limit - Hitachi Relion 670 Series Commissioning Manual

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.13.14.1

Function revision history

Document
revision
A
B
C
D
E
F
G
H
11.13.14.2

Verifying the signals and settings

The Fault locator function LMBRFLO depends on other functions to work properly, that is, phase
selection information from distance protection function and analog information supplied by the trip
value recorder function. Check that proper binary start and phase selection signals are connected
and voltage and current signals are configured (parameter settings).
The result is displayed on the local HMI or via PCM600. Distances to faults for the last 100 recorded
disturbances can be found on the local HMI under Main menu/Disturbance Records /Disturbance
#n(n = 1–100)/General Information
If PCM600 is used, the result is displayed on the recording list after upload, including loop selection
information.
Table 24:
Parameter
I
Healthy conditions
Impedance |Z|
Impedance angle ZF
11.13.14.3

Measuring the operate limit

1.
Set the test point (|Z| fault impedance and ZF impedance phase angle ) for a condition that
meets the requirements in
2.
Subject the IED to healthy normal load conditions for more than the prefault recording time in
DRPRDRE function.
3.
Apply a fault condition.
200
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Added FLINVAL, FLT_DIST, FLT_R, and FLT_LOOP outputs in the ACT function block.
2.2.5
-
Test settings
Condition
Higher than 30% I
U = 63,5 V, I = 0 A & ZF = 0°
Test point
Note:
Test angle
Table
© 2017 - 2022 Hitachi Energy. All rights reserved
r
£ (X0 + 2 · X1)/3 For single-phase faults
Z
x
£ X1 For three and two phase faults
Z
x
£ (X0 + 2 · X1 XM)/3 For single-phase fault with mutual zero-sequence
Z
x
current
ZF arctan[(X0 + 2 · X1) / (R0 + 2R1)] For single-phase faults
ZF arctan(X1/R1) For two-phase faults
24.
1MRK 511 403-UEN Rev. L
GUID-1740AA05-417C-4474-ABE7-F15CB4D16019 v3
GUID-0FDCCF3B-63C5-463E-AD67-2AE3633E9CE9 v1
M14955-48 v7
Bay control REC670
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents