If the limit values of a plant are known, and if the CO limit need not be remeasured, the
O2 min. values can be entered directly.
P
o
i
n
t
O
2
M
i
P
A
i
r
On the first line, Point, select the point number to be changed and confirm by pressing
Enter (point 1 can be adjusted). With the second line, O2 Min Value, the O2 min. value
can be directly parameterized. The points are approached only if, previously, setting
choice P-Air Man has been used.

19.11.4 Measuring the O2 min. values by lowering the air rate

On the first line, select the point number and confirm by pressing Enter. Now, select
line P-Air Man and confirm. After confirming with Enter, the fuel-air ratio control system
approaches this point on the parameterized ratio control curve, that is, air rate reduction
P-Air Man is set to «0». The display on the second line changes to Actual O2 Value,
which will then be displayed.
P
o
i
n
t
A
c
t
O
P
A
i
r
By readjusting the air rate P-Air Man, the amount of combustion air and thus the O2
value can be reduced. P-Air Man corresponds to the relative air rate reduction. During
the readjustment, all actuators on the curve parameterized as air influen will travel to
the relevant positions. When the O2 min. value is found, the acquired Actual O2 Value
is entered as the O2 Min Value by pressing Enter.