Charging Refrigerant - LG ARUN363DDA4 Installation Manual

Split rooftop unit(rtu)
Table of Contents

Advertisement

CHARGING REFRIGERANT

DANGER
Refrigerant gas is heavier than air and replaces oxygen. A massive leak will result in oxygen depletion, especially in basements,
and an asphyxiation hazard will result in serious injury or death.
If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas will result in producing toxic gas if it
comes into contact with fire. Exposure to this gas will result in severe injury or death.
WARNING
Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the leak test and the vacuum drying.
When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of
liquid hammer.
Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant
R410A is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when charging refrigerant.
When the refrigerant system is to be opened, refrigerant must be treated according to the applicable legislation.
To avoid compressor breakdown.
Refrigerant Charge Worksheet
The calculation of the additional charge should take into account the length of pipe and CF (Correction Factor) value
of RTU unit.
Job Name : _____________________________________________
System Tag or ID
Project Manager : ________________________________________
Line #
1
Linear feet of 1/4" liquid line tubing
2
Linear feet of 3/8" liquid line tubing
3
Linear feet of 1/2" liquid line tubing
4
Linear feet of 5/8" liquid line tubing
5
Linear feet of 3/4" liquid line tubing
6
Linear feet of 7/8" liquid line tubing
7
Linear feet of 1" liquid line tubing
8
Split Rooftop Unit
ADDTIOINAL Refrigerant Charge Required (Sum of lines 1-8)
9
10
Outdoor Unit Factory Refrigerant Charge
Total ODU FACTORY Refrigerant Charge
11
(sum of factory refrigerant charges for all ODUs in the system, line 10A – 10H)
TOTAL SYSTEM CHARGE
12
Sum of Additional Refrigerant Charge Required
1
CF (Ref.) = Correction Factor for Refrigerant Charge.
2
For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Do not charge the refrigerant more than the specified amount.
Description
2
2
2
2
2
2
2
10A
10B
10C
10D
10E
10F
10G
10H
(line 9)
Due to our policy of continuous product innovation, some specifications may change without notification.
Chassis
Size
I.D
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DD
72k
ARUM072*TE5
72k
ARUM096*TE5
96k
ARUM121*TE5
121k
ARUM144*TE5
144k
ARUM168*TE5
168k
ARUM192*TE5
192k
ARUM216*TE5
216k
ARUM241*TE5
241k
and Total ODU Factory Refrigerant Charge
Date : ______________
1
Quantity
CF(Ref.)
Total(lbs.)
0.015
0.041
0.079
0.116
0.179
0.238
0.323
1.61
14.3
23.2
23.2
26.5
26.5
30.9
37.5
37.5
(line 11)
38

Advertisement

Table of Contents
loading

Table of Contents