9.4.3 Maintenance

9.4.3.1 Deleting a device
9.4.3.2 Accepting replaced/exchanged devices
A6V10421795_en--_k
Device deletion is not supported on the panel. It can only be done in the online
configuration tool. See document
delete a device.
After replacing faulty devices with new ones or exchanging device locations within
the same ↑ detector line, perform the command of 'Accept replaced devices' to
acknowledge device replacement or location exchange. The newly replaced or
exchanged devices inherit all features and parameter settings from the old devices.
Before accepting newly replaced or exchanged devices, note the following:
Ensure newly replaced devices are of the same type with devices to be
replaced.
Ensure newly exchanged devices are of the same type and within the same
detector line with devices to be exchanged.
Power off the detector line before uninstalling and replacing faulty devices.
Ensure no devices are left out when exchanging device locations.
Do not change the topology when replacing or exchanging devices.
To accept replaced/exchanged devices
 The detector line is powered off. See 'Power off [➙ 90]'.
1. Press
on the keypad.
 The 'Main menu' window is open.
2. Select 'Engineering' and press
 The 'Engineering' window is open.
3. Select 'Detector line' and press
 The 'Detector line' window is open.
4. Select 'Maintenance' and press
 The 'Maintenance' window is open.
5. Select 'Accept replaced devices' and press
 A list of all lines is displayed.
6. Select a line and press
 A confirmation dialog window is open.
7. Press
to confirm.
 The replaced/exchanged devices are accepted.
A6V10450595
for detailed information on how to
.
.
.
.
.
Engineering
9
Detector line
91 | 151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents