FusionModule2000 Smart Modular Data Center
Product Description
Item
Expansion bolt hole
Storage temperature
Storage humidity
Maximum operating pressure
7.5.4 (Optional) Sunshade
When an outdoor unit is used in the T3 working condition (–5° C to +55° C), install a sunshade
if the following three conditions are met.
If the previous three conditions are met but no sunshade is installed, the smart cooling product
will shut down because the components are applied beyond specifications.
Figure 7-17 Sunshade appearance
Issue 06 (2020-05-21)
The outdoor unit is installed horizontally.
The ambient temperature exceeds 50° C.
The outdoor unit is directly exposed to sunlight.
Copyright © Huawei Technologies Co., Ltd.
7 Temperature Control System
Specifications
M12x60
–40° C to +70° C
5%–95% RH (non-condensing)
4.35 MPa
133