The data points are the measured variables of the Modbus device.
The attributes relevant for integrated services can be set with powerconfig.
Description of a data point
Attributes of a data
Description
point
Language-specific
In the 7KN Powercenter 3000, data points are handled in various lan-
name
guages, e.g. in the web user interface. These names can be defined for the
individual languages here.
Uniform name
This attribute is optional. It is used by 7KN Powercenter 3000 for uniform
handling of such data points across all device types.
These are currently the SENTRON powermind and the project Export (json,
csv).
A data point can be assigned to one of these selectable uniform names.
Category
Assignment of the data point to one of the defined categories
Register address
Register address [0001, 65535] of the data point must be entered in the
Modbus device. The register address 0 is used as the default value. I.e. this
address is not actively used.
Register count
Number [1.125] of register addresses occupied by the data point.
Byte offset
Byte position within the addressed register from which the data are inter-
preted.
Byte count
Number of bytes that are interpreted.
Bit offset
Bit position within the addressed register from which the data are inter-
preted.
Bit count
Number of bits that are interpreted.
Data format
The format for the data point must be chosen here. For details, see the
table Supported data formats below.
Scaling factor
This factor must be applied to the value.
E. g. at frequency 0.01: Value 5015 x 0.01 = 50.15 Hz
Display format
In this way, display of the value on a user interface, e.g. the web user inter-
face of the 7KN Powercenter 3000 can be controlled.
Unit
Basic unit of the value, such as A, V, W
Runtime settings
The setting(s) control processing of the value by 7KN Powercenter 3000
Archiving
On → Values are archived every 10 seconds and 15 minutes.
Off → No archiving
In particular in existing Modbus devices, several data points, e.g. individual statuses, are
shown partly in a Modbus register. With these attributes, several data points can be read out
of the same register.
Individual data points on a Modbus address are addressed according to the following system.
7KN POWERCENTER 3000
Equipment Manual, 07/2020, L1V30579222003-03
Scaling: Values with the most significant 4 decimal places.
Counter value: The value is displayed with all its digits.
K count value: The value is displayed with all its digits and k (= Kilo).
Boolean: 0 → "No", 1 → "Yes"
Text: Value is displayed as text.
Functions
5.9 Modbus devices
Notes
= Uniform Name
See Example for ad-
dressing a data point
(Page 84)
See the table Support-
ed data formats below
(Page 85)
Depending on the time
zone chosen, a suitable
decimal separator e.g.
"." in the USA or "," in
Europe is used.
For numeric data
points only