NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
Alar
m ID
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A208
-01
A220
-01
Issue 06 (2020-08-19)
Alarm
Alarm Name
Severit
y
MAJOR
Indoor fan 3
blocked alarm
MAJOR
Indoor fan 4
blocked alarm
MAJOR
Indoor fan 5
blocked alarm
MAJOR
Indoor fan 6
blocked alarm
MAJOR
Exhaust fan 1
blocked alarm
MAJOR
Exhaust fan 2
blocked alarm
MAJOR
Exhaust fan 3
blocked alarm
MAJOR
Exhaust fan 4
blocked alarm
MAJOR
Exhaust fan 5
blocked alarm
MAJOR
Exhaust fan 6
blocked alarm
WARNI
Wizard
NG
startup is in
progress
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Probable Cause
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
1. The fan blade is
stuck.
2. The fan is faulty.
Wizard startup is in
progress.
Solution
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Clear the blockage.
2. Maintain or replace
the fan.
1. Wait until wizard
startup is complete or
clear the Wizard
startup in progress
alarm manually to exit
wizard startup.
166