08/2005
Cause:
The 24 V power supply for the digital outputs is missing.
Alarm value (r2124, hexadecimal):
01: TM17 24 V power supply for DI/DO 0 ... 7 missing.
02: TM17 24 V power supply for DI/DO 8 ... 15 missing.
04: TM15 24 V power supply for DI/DO 0 ... 7 (X520) missing.
08: TM15 24 V power supply for DI/DO 8 ... 15 (X521) missing.
10: TM15 24 V power supply for DI/DO 16 ... 23 (X522) missing.
20: TM41 24 V power supply for DI/DO 0 ... 3 missing.
Remedy:
Check the terminals for the power supply voltage (L1+, L2+, L3+, M).
235907
<location>TM: Hardware initialization unsuccessful
Reaction:
NONE
Acknowledge:
NONE
Cause:
The terminal module was not successfully initialized.
Alarm value (r2124, hexadecimal):
01: TM17 or TM41 - incorrect configuration request.
02: TM17 or TM41 - programming not successful.
04: TM17 or TM41 - invalid time stamp
Remedy:
Carry-out a POWER ON.
235910
<location>TM: Module overtemperature
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature in the module has exceeded the highest permissible limit.
Remedy:
- reduce the ambient temperature.
- replace the terminal module.
235911
<location>TM: PROFIBUS: Clock synchronous operation sign-of-life
missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum permissible number of errors in the master sign-of-life (clock synchronous
PROFIBUS) has been exceeded in cyclic operation.
When the alarm is output, the module outputs are reset up to the next synchronization.
Remedy:
- check the physical bus configuration (terminating resistor, shielding, etc.).
- check the interconnection of the master sign-of-life (r4201 via p0915).
- check whether the master correctly sends the sign-of-life (e.g. set-up a trace with
r4201.12 ... r4201.15 and trigger signal r4301.9).
- check the bus and master for utilization level (e.g. bus cycle time Tdp was set too short).
235920
<location>TM: Temperature sensor fault
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, decimal):
1: Wire breakage or sensor not connected (KTY: R > 1630 Ohm).
2: Measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Remedy:
- check that the sensor is connected correctly.
- replace sensor.
235999
<location>TM: Unknown alarm
Reaction:
NONE
Acknowledge:
NONE
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-793