Network with
RX... room
controllers
Area 0
Ac 1.0.0
1)
N140/13
Heat distr zone
Refrig distr zone 16
Lc 1.1.0
1)
N140/13
Heat zone source
Refrig zone source
Heat zone consumer 1
Refrig zone consumer 1
LTE filter table: 1) Normal (route), 2) Route all, 3) Block all
88/120
Building Technologies
HVAC Products
The recommendation on the previous page is particularly important in relation to a
network with a large number of RX... room controllers.
In a line containing up to 62 RX... room controllers, an RMB795 central control unit
is used as a "collector". The area/line couplers are set to "Normal (route)".
The heating and refrigeration distribution zone in each RX... room controller is con-
figured with a zone address in the range 1...15 (data communication within the line).
The heating and refrigeration distribution zone in each RX... room controller is
configured on the consumer side with a zone address in the range 16...13 (data
communication via area/line coupler).
The heating/refrigeration demand from the RX... room controllers is transmitted by
the "collector" to the RMH primary heating and RMU primary cooling controllers.
ACS alarm
pager, SMS, fax
0.2.150
OZW775
1.0.1
RMH
16
1.0.2
RMU
Main line 1
16
16
1.1.1
RMB...
1.1.2
Heat distr zone
1
Refrig distr zone
1
RX...
Heat distr zone
1
Refrig distr zone
1
1.1.64
Heat distr zone
1
Refrig distr zone
1
RX...
Basic documentation: Communication via the KNX bus
Large plants
0.2.254
Sercice cable
Service-
Interface
RJ45
connector
Bus connector
socket
Ac 2.0.0
1)
N140/13
2.0.1
RM...
2.0.2
RM...
2.0.20
Heat distr zone
Refrig distr zone
RX...
2.0.21
Heat distr zone
Refrig distr zone
RX...
Lc 1.15.0
1)
N140/13
Heat zone source
Refrig zone source
1.15.1
RMB...
Heat zone consumer 1
Refrig zone consumer 1
1.15.2
Heat distr zone
Refrig distr zone
RX...
Heat distr zone
62 RX...
Refrig distr zone
1.15.64
Heat distr zone
Refrig distr zone
RX...
USB
PC with ACS
3)
16
16
2 RX...
16
16
2)
16
16
1
1
1
62 RX...
1
1
1
0.2.252
RMZ792
Ac 15.0.0
N140/13
15.0.1
RM...
15.0.2
RM...
15.0.3
RM...
15.0.4
RM...
Main line 15
Lc 15.1.0
N140/13
Bus power supply
+
AC 120...230 V
~
-
N125/x1
15.1.1
RX...
15.1.2
RX...
4 RX...
15.1.3
RX...
15.1.4
RX...
CE1P3127en