Siemens LMV5 Series Basic Documentation page 219

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A6
53
LC
A6
54
LC
A6
55
LC
A6
56
LC
A6
57
LC
A6
58
LC
A6
59
LC
A6
5A
LC
A6
60
LC
A6
61
LC
A6
62
LC
A6
63
LC
A6
64
LC
A6
65
LC
A6
66
LC
A6
67
LC
A6
68
LC
A6
69
LC
A6
6A
LC
A6
6B
LC
A6
6C
LC
A6
6D
LC
A6
6E
LC
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Short-circuit Pt1000 Sensor
Short-circuit sensor PT1000 (X60.3 X60.4) Check wiring and sensor
Open-circuit PT1000 Sensor
Open-circuit sensor PT1000 (X60.3
X60.4)
Short-circuit Ni1000 Sensor
Short-circuit sensor Ni1000 (X60.3 X60.4) Check wiring and sensor
Open-circuit Ni1000 Sensor
Open-circuit sensor Ni1000 (X60.3 X60.4) Check wiring and sensor
Overvoltage at Input 2
Overvoltage at input 2 (X61)
Open-circuit / Short-circuit at
Open-circuit / short-circuit input 2 (X61)
Input 2
Overvoltage at Input 3
Overvoltage at input 3 (X62)
Open-circuit / Short-circuit at
Open-circuit / short-circuit input 3 (X62)
Input 3
Internal Fault Load Controller
Timeout during calibrate_ADC
Internal Fault Load Controller
Timeout during read_conversion
Internal Fault Load Controller
Timeout during calibrate_ADC
Internal Fault Load Controller
Fault during RedInv reading from A/D
converter
Internal Fault Load Controller
Fault internal A/D converter
Internal Fault Load Controller
Gain register has been changed
Internal Fault Load Controller
Offset register has been changed
Internal Fault Load Controller
Too great / small gain for self-calibration
of A/D converter
Internal Fault Load Controller
Too great / small offset for self-calibration
of A/D converter
Internal Fault Load Controller
Fault internal A/D converter
Internal Fault Load Controller
Fault during PWM test
Internal Fault Load Controller
Faulty reference voltage
Internal Fault Load Controller
Fault transmitter power supply
Internal Fault Load Controller
Fault analog output, voltage deviation too
great
Internal Fault Load Controller
Fault during resistance test PT100 input
(X60)
Meaning for the LMV5x system
Troubleshooting
Check wiring and sensor
Check wiring and sensor
Check wiring and sensor
Check wiring and sensor
Check wiring and sensor
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
*1)
219/278