SINAMICS S120 Fail-Safe Drives
The use of the safety functions integrated in the drive has been selected
and these can now be activated or deactivated using the operator elements
at the F-CPU.
Only the following messages should be visible
These messages doe not influence the functionality described above.
6.7

Acceptance test

To verify the safety-related parameters, when commissioning the machine
for the first time and also when making changes to the safety-relevant pa-
rameters, an acceptance test must be carried-out. It is imperative that the
acceptance test must be correspondingly logged and documented. The ac-
ceptance reports should be appropriately stored and archived.
The acceptance test must be performed after parameterization has been
completed and power-on reset.
Information about the acceptance test, the acceptance report and an ex-
ample of corresponding acceptance report are provided in the "Function
Manual SINAMICS S120 Safety Integrated" (FHS) in the chapter, Accep-
tance test and acceptance report.