2 Solution

2
Solution
2.1

Overview of the overall solution

Schematic
The following schematic diagram shows the most important components of the
solution:
Figure 2-1: Relative components of the safety functions
Controlling safety functions STO and SLS via PROFIsafe with PROFINET for a
SINAMICS S120 drive line-up is demonstrated using this application example.
PROFIsafe telegram 901 can be used to control the safety function and also enter
a safety-relevant speed limit.
The drive line-up in the booksize format comprises an infeed and a Double Motor
Module (DMM). A CU320-2 Control Unit is used to control the motor. The extended
setpoint channel is used to enter a speed setpoint. The servomotor is controlled
using the Double Motor Module. A Smart Line Module (SLM) is used as infeed.
The safety-related signals are sensed using fail-safe inputs of the F-CPU and
evaluated in the F-CPU. The safety functions integrated in the drive are controlled
via the fail-safe PROFIsafe communication.
A variable SLS limit is entered depending on the states of the signals of the
protective door and the light barrier. The F-CPU evaluates the signals, and
10
PROFIsafe SLS Override
Version 1.0, Entry ID: 81682475