Siemens SINAMICS S120 Function Manual page 75

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Activate test mode (p10041)
A check mark at an F-DI defines whether the pair of digital inputs is to be integrated in the
forced dormant error detection test of the assigned power supply (L1+ or L2+) (for additional
information, refer to the chapter "Forced dormant error detection", under Extended
Functions).
LED in F-DI screen
The LED downstream of the AND element indicates the logical state (inactive: gray, active:
green, discrepancy error: red).
Outputs screen F-DO
Figure 6-4
Outputs screen
Signal source for F-DO (p10042 - p10045)
An AND element with 6 inputs is interconnected with each output terminal pair of an F-DO;
the signal sources for the AND inputs can be selected:
● No signal source (input set to logical HIGH; default)
● Status signals of the drive of drive group 1 to 4
Test selection F-DO (p10046 [0..3])
The test stop for forced dormant error detection can be activated for each F-DO by means of
a pull-down menu (for additional information, refer to the chapter "Forced dormant error
detection", under Extended Functions).
Safety Integrated
Function Manual, (FHS) , 07/2007 Edition, 6SL3097-2AR00-0BP0
For additional information on status signals, refer to the chapter "F-DO overview" in the
"Control by means of TM54F terminals".
6.2 Commissioning TM54F by means of STARTER/SCOUT
Commissioning
75