4.2
Internal jumpers
16
Building Technologies
Fire Safety & Security Products
Unit
Switch S1-5
Switch S1-6
Address
↓
0
Off
Off
↑
1
On
Off
↓
2
Off
On
3
↑
On
On
4
↓
Off
Off
5
↑
On
Off
↓
6
Off
On
↑
7
On
On
↓
8
Off
Off
↑
9
On
Off
↓
10
Off
On
11
↑
On
On
12
↓
Off
Off
13
↑
On
Off
14
↓
Off
On
↑
15
On
On
Tab.7.
DF8000 unit address settings
Note that the DF8003 units that include 4 to 6 I/O modules, i.e. the double units,
always allocate two consecutive addresses on the RS485 line: the address se-
lected on S1-5 to S1-8 and the subsequent one. This applies both to even and odd
addresses.
On the front panel, the CPU module has also a reset button that can generate
hardware reset on the CPU microprocessor.
Internally, 6 jumpers (J1...J6) are available to reverse the 0/1 logic on each of the
six I/O modules (positive or negative logic). If the jumper is installed, then the cor-
responding I/O modules functions with positive logic (see Fig. 8).
1
8
S2
S1
1
Fig. 8
CPU module - board layout
Switch S1-7
Switch S1-8
↓
↓
Off
Off
↓
↓
Off
Off
↑
↓
Off
Off
↑
↓
Off
Off
↓
↑
On
Off
↓
↑
On
Off
↑
↑
On
Off
↑
↑
On
Off
↓
↓
Off
On
↓
↓
Off
On
↑
↓
Off
On
↑
↓
Off
On
↓
↑
On
On
↓
↑
On
On
↑
↑
On
On
↑
↑
On
On
J1
CPU
I/O logic jumpers
J6
(installed means positive logic, 0 =
inactive and 1 = active)
048_DMS_DF8000_ICC_MP4.15_A6V10081388_c_en.doc
Notes
↓
↓
↓
↓
↓
↓
↓
↓
↑
↑
↑
↑
↑
↑
↑
↑
Not valid for double units
06.2008