2-Address (-Unit) Dependence; Reset Of 2-Zone / 2-Address Dependence; Alarm; Delayed Alarm - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
13.8.2
13.8.3
13.9

2-address (-unit) dependence

Each analog detector, addressable multipurpose I/O unit (3361)
monitored Input 0 (Z) and 8 zones expansion board (4580) input, can
be programmed for 2-unit dependent fire alarm activation. (Heat
detectors should not and manual call points must not be 2-unit
dependent).
Function:
Two or more units in the same zone have to be in "fire alarm state"
at the same time to activate a fire alarm in the control unit. When only
one unit is in "fire alarm state" it is indicated in the control unit (c.i.e.)
as follows:
The buzzer sounds like for pre-warning (0.8 / 5 sec.).
In the c.i.e. LCD the following information is shown:
Co-incidence alarm detector ZZ/AA
Programmable outputs can be activated by trigger condition "Two
Address Dependent Fire Alarm" but no other outputs will be activated.
A co-incidence alarm can be manually reset ("Reset" button on the
front) and will be automatically reset 5 min. after it is no longer in
"fire alarm state".
Reset of 2-zone / 2-address dependence (co-incidence

alarm

The unit / zone having activated a Co-incidence alarm will be latched
in this status for at least 5 minutes and then automatically reset.
During these 5 minutes the push button "Reset", on the c.i.e. front /
FBP, can be used to manually reset the Co-incidence alarm.
If, during these 5 minutes, at least one more unit (in the zone) or at
least one more zone (in the group) comes into "fire alarm state", the
Co-incidence alarm ends and normal fire alarms will be activated in
the c.i.e.

Delayed alarm

In some premises delayed fire alarm activation can be used to avoid
unwanted false alarms (nuisance alarms). The delay time will be
added at the end when a fire alarm normally would have been
activated in the c.i.e. This function is a violation to the EN54-2
standard.
Each analog or addressable detector, each addressable multipurpose
I/O unit (3361) monitored input (Z) and 8 zones expansion board
(4580) input in the system can be programmed (in EBLWin) to
delayed fire alarm activation. (Heat detectors should not and manual
101
EBL128 Planning Instructions V2.0.x
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents