Huawei NetCol8000-E220 User Manual page 98

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220:
Table of Contents

Advertisement

NetCol8000-E220 Modular Indirect Evaporative Cooling
System
User Manual
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in
Figure 4-18 Teamwork topology
Table 4-9 Notes for the screen
No.
1
2
3
4
5
Issue 02 (2019-10-10)
2.
Figure
Parameters
Note
On/Off
On indicates that the smart cooling product is started and Off
indicates that the smart cooling product is shut down.
01, 02, 03
Indicates the device address. The minimum address is the master
one and the rest are all slave ones.
NOTE
If the master one offline, the online device with the smallest address is
selected to be the new master.
Active/Stand
Active: properly responds to the requirement control.
by
Standby: responds to the requirement control when active one is
faulty (critical alarms, shutdown, and offline) or cannot meet
cooling requirements.
M indicates the master unit, and S indicates a slave unit. Blue
M/S
indicates that the device is operating, and gray indicates that the
device is idle.
Frame:
A device with green frame indicates the device itself,
green/non-gr
een
as shown in
A non-green frame indicates the other device in the group,
Copyright © Huawei Technologies Co., Ltd.
4-18.
Table 4-9
describes the note for the screen.
.
4 Power-on and Commissioning
Step 1
. If the
and
90