1MRS759142 C
4.12.4.4
4.12.4.5
REX640
Technical Manual
SRCPTOC contains a blocking functionality. It is possible to block function outputs,
timers or the function itself.

Analog input configuration

SRCPTOC has one analog group input which must be properly configured.
Table 984:
Analog inputs
Input
I3P
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of SRCPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
I_A
Resonance
I_B
I3P
current
I_C
calculation
RESO_IN
Blocking
BLOCK
GUID-02932E2B-FF44-463F-916C-9E8B0D997636 V1 EN
Figure 563:
Functional module diagram
Resonance current calculation
This module calculates the resonance current per phase set as per setting Tuning
harmonic Num. The resonance current for phase A is calculated with the equation.
Description
Three-phase currents
Timer 1
Level
detector 1
Timer 2
Level
detector 2
logic
Section 4
Protection functions
t
ALARM
t
OPERATE
1045