GE AF-650 GP Design Manual page 135

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
HP
0.33-1
2-3
5
7.5-10
15
20-25
30
40
50
HP
0.5-2
3-5
7.5-10
15-25
30
40
50
7
60
75-100
* Type gG is not applicable to frame sizes C2 in IP21 enclosure and frame size C4. In this case type aR is recommended.
15-30 HP
40 HP
50 HP
60 HP
75-100 HP
125-300 HP
350-550 HP
1) Max. fuses - refer to national/international regulations to select an appropriate fuse size.
134
1)
Max. fuse size
10A
20A
32A
63A
80A
125A
160A
200A
250A
Max. fuse size
1)
10A
20A
32A
63A
80A
100A
125A
160A
250A
Max. fuse size
1)
63 A
80 A
100 A
125 A
160 A
380 - 480 V
380 - 480 V
Min. rated Voltage
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
200-240 V
Min. rated Voltage
380-480 V
380-480 V
380-480 V
380-480 V
380-480 V
380-480 V
380-480 V
380-480 V
380-480 V
Voltage
525 - 690 V
525 - 690 V
525 - 690 V
525 - 690 V
525 - 690 V
type gG
type gR
AF-650 GP Design Guide
Type
type gG
type gG
type gG
type gG
type gG
type gG
type aR
type aR
type aR
Type
type gG
type gG
type gG
type gG
type gG
type gG
type gG
type gG*
type gG*
Type
type gG
type gG
type gG
type gG
type gG

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents