Class Code 005 (0x05): Connection Object

The Connection Class allocates and manages the internal resources associated with both I/O and Explicit
Messaging connections. The specific instance generated by the Connection Class is referred to as a Con-
nection Instance or a Connection Object.
Three instances of the Connection Class will be supported. Instance 1 will be the Explicit Message Con-
nection, instance 2 will be the Polled I/O Connection, and instance 4 will be the COS/Cyclic IO Connec-
tion.
Class Attributes
None
Instance Attributes
Connection Object, Instance 1 = Explicit Message Connection, Attributes
Attribute
Access
Name
1
Get
State
2
Get
Instance Type
3
Get
Transport Class Trigger
4
Get
Produced Connection ID
5
Get
Consumed Connection ID
6
Get
Initial Comm. Characteristics
7
Get
Produced Connection Size
8
Get
Consumed Connection Size
9
Get/Set
Expected Packet Rate
12 (0x0C)
Get/Set
Watchdog Timeout Action
13 (0x0D)
Get
Produced Conn. Path Length
14 (0x0E)
Get
Produced Connection Path
15 (0x0F)
Get
Consumed Conn. Path Length
16 (0x10)
Get
Consumed Connection Path
17 (0x11)
Get
Production Inhibit Time
*1) Connection state
0
nonexistent
1
configuring
2
wait for connection ID
3
established
4
timed out
5
deferred
*2) xxxxxx = node address
*3) The size of Produced and Consumed Connection depends on the device connected to the DNP31 (as
of writing UMC100.3). For detailed information, please refer to the device manual.
DNP31.0 Data sheet
Type
Value
USINT
*1)
USINT
0 = Explicit Message
BYTE
0x83 - Server,
Transport Class 3
UINT
10xxxxxx011
UINT
10xxxxxx100
BYTE
0x21
UINT
*3)
UINT
*3)
UINT
in ms
USINT
01 = auto delete
UINT
0
EPATH
Empty
UINT
0
EPATH
Empty
UINT
0