Table 65. Motor load jam protection (JAMPTOC) main settings
Parameter
Operation
Start value
Operate delay time
Table 66. Motor start-up supervision (STTPMSU)
Characteristic
Operation accuracy
Start time
52, 53
IFault = 1.1 × set Start detection A
Operate time accuracy
Reset ratio
Table 67. Motor start-up supervision (STTPMSU) main settings
Parameter
Motor start-up A
Motor start-up time
Lock rotor time
Operation
Operation mode
Restart inhibit time
Table 68. Phase reversal protection (PREVPTOC)
Characteristic
Operation accuracy
Start time
54, 55
IFault = 2.0 × set Start value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
Table 69. Phase reversal protection (PREVPTOC) main settings
Parameter
Start value
Operate delay time
Operation
52 Current before = 0.0 × In, fn = 50 Hz, overcurrent in one phase, results based on statisti-
cal distribution of 1000 measurements
53 Includes the delay of the signal output contact
54 Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribu-
tion of 1000 measurements
55 Includes the delay of the signal output contact
ABB
Function
JAMPTOC
JAMPTOC
JAMPTOC
Value
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Minimum
29 ms
±1.0% of the set value or ±20 ms
Typically 0.90
Function
STTPMSU
STTPMSU
STTPMSU
STTPMSU
STTPMSU
STTPMSU
Value
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Minimum
24 ms
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Function
PREVPTOC
PREVPTOC
PREVPTOC
Value (Range)
1 = on
5 = off
0.10...10.00 × In
100...120000 ms
Typical
30 ms
Value (Range)
1.0...10.0 × In
1...80 s
2...120 s
1 = on
5 = off
1 = IIt
2 = IIt, CB
3 = IIt + stall
4 = IIt + stall, CB
0...250 min
Typical
25 ms
Value (Range)
0.05...1.00 x In
100...60000 ms
1 = on
5 = off
1MRS758725
Step
-
0.01
10
Maximum
34 ms
Step
-
1
Maximum
28 ms
Step
0.01
10
-
23