Restart - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01457
Rev: -
22
Action
Control unit power OFF
then power ON again.
RESET jumper JP4 on the
main board 1556.
Reset command from Win512
or TLON Manager
Automatically due to external
disturbance.
Automatically after download
of site specific data (SSD) via a
PC & Win512.
Operating Instructions Fire alarm system EBL512, V2.7.x

Restart

87
A restart
will delete or not delete the data in the control unit. Here
follow an explanation of the different data, abbreviations and a table
showing how the data respectively is affected.
FFD = Fire alarms, faults and disablements.
SSW = Week average sensor values, access codes, supervised output
calibration values and log buffers. (Alarm counter when applicable.)
SSD = Site specific data, i.e. all the installation programming
downloaded from Win512.
SSI = EBL512 settings downloaded from Win512.
S/W = Software, i.e. the control unit system program.
Safe shut down of control unit (menu H8/S8) will save the SSW
data in a Flash ROM before you power off (de-energize)
unit. Before the first "Safe shut down" this memory is empty. After
each "Safe shut down", the latest SSW data is saved. When the power
supply returns, the control unit RAM (working memory) will, after the
restart, read the SSW data saved in the Flash ROM.
90
and
91
NOTE! During restart, the following will happen:
-- The Fault tx relay output will be "activated".
87
Restart affects the control unit where it is performed and that control unit's
data in a system.
88
A restart via jumper JP4 or an external disturbance might also delete the
SSW if the restart is in the middle of an un-controlled process.
89
If this memory is empty when the power supply returns, new week
average sensor values will be calculated within two minutes. During the two
minutes all fire alarms from analog smoke detectors will be suppressed.
90
See "Safe shut down of control unit" above.
91
If this happens often, call for service personnel / engineer.
88
Data, etc. which
Data, etc. which
will be deleted
will be not deleted
90
SSW
SSD, SSI,
FFD
S/W
88
FFD (SSW)
SSD, SSI,
S/W, SSW
FFD
SSD, SSI,
S/W, SSW
88
FFD (SSW)
SSD, SSI,
S/W, SSW
FFD
SSD, SSI,
S/W, SSW
88
the control
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents