Technology instructions
9.2 PID control
Parameter and type
ManualUP
IN
ManualDN
IN
ErrorAck
IN
Reset
IN
ModeActivate
IN
Mode
IN
ScaledInput
OUT
ScaledFeedback
OUT
Output_UP
OUT
430
Data type
Description
Bool
Manual_UP = TRUE:
The valve is opened even if you use Output_PER or a position
feedback. The valve is no longer moved if the high end stop has
been reached.
See also Config.VirtualActuatorLimit
Manual_UP = FALSE:
If you use Output_PER or a position feedback, the valve is
moved to ManualValue. Otherwise, the valve is no longer
moved.
Note: If Manual_UP and Manual_DN are set to TRUE simultaneously,
the valve is not moved.
Bool
Manual_DN = TRUE:
The valve is opened even if you use Output_PER or a position
feedback. The valve is no longer moved if the high end stop has
been reached.
See also Config.VirtualActuatorLimit
Manual_DN = FALSE:
If you use Output_PER or a position feedback, the valve is
moved to ManualValue. Otherwise, the valve is no longer
moved.
Bool
Resets the ErrorBits and warning outputs. FALSE to TRUE edge
Bool
Restarts the controller. (Default value: FALSE):
FALSE to TRUE edge:
Switches to "inactive" mode
Resets the ErrorBits and warning outputs
Clears Integral action
Maintains PID parameters
As long as Reset = TRUE, PID_3Step remains in "Inactive" mode
(State = 0).
TRUE to FALSE edge:
PID_3Step switches to the operating mode that is saved in the
Mode parameter.
Bool
The PID_3Step switches to the mode that is saved in the Mode
parameter. FALSE to TRUE edge:
Int
The desired PID mode; Activated on the leading edge of the Mode
Activate input.
Real
Scaled process value
Real
Scaled valve position feedback
Note: For an actuator without position feedback, the position of the
actuator indicated by ScaledFeedback is very imprecise.
ScaledFeedback can only be used for rough estimation of the current
position in this case.
Bool
Digital output value for opening the valve. (Default value: FALSE)
If Config.OutputPerOn = FALSE, the parameter Output_UP is used.
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG