D. Power Consumption – D20 Modules - GE D20 Technical Overview

Remote terminal unit
Hide thumbs Also See for D20:
Table of Contents

Advertisement

D20/D200 Technical Overview
D. Power Consumption – D20 Modules
D20ME
D20S
D20A
D20K
D20K O/B Relay
D20C
D20C A/I
D20C I/O
Rack Modem
Universal Protocol Converter
48 V Status Point
24 V Status Point
130 V Status Point
For example, a D20S with 8 points on using 24V wetting has a typical power consumption of:
3.00W + 8(0.132W) = 4.056W
A D20K with 4 relays operating requires:
4.00W + 4(0.288W) = 5.152W
92
Power Consumption (Typical Watts)
Module
PRPI-019-3.00-10
GE Grid Solutions
4.00
3.00
7.00
4.00
0.288
5.00
1.50
1.50
1.44
0.680
0.264
0.132
0.715
GE Information

Advertisement