Properties
1.1 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Noise suppression for
f = n x (f1 ± 1 %), (f1 = interference frequency)
•
•
Crosstalk between the inputs
Operational limit for ±80 mV (over the entire
temperature range with reference to the input
range)
Operational limit for thermocouples (over the
entire temperature range with reference to the
input range)
Operational limit for thermocouple type C (in the
entire temperature range with reference to the
input range)
Basic error limit for ±80 mV (operational limit at
25 °C with reference to the input range)
Basic error limit for thermocouples (operational
limit at 25 °C with reference to input range)
Basic error limit for thermocouples of type C
(operational limit at 25 °C with reference to the
input range)
Temperature error (with reference to the input
range)
Linearity error (with reference to the input range)
Repeatability
(in steady state at 25°C with reference to input
range)
Overall error limits using internal compensation
•
•
Input range (rated value)/input resistance
•
•
Permitted input voltage (destruction limit)
Connection of the sensors
•
Characteristic curve linearization
10
Common-mode interference (U
Series-mode interference
(peak interference value < rated value of input
range)
1
1
1
Operational limit (in the entire temperature
range with a static, thermal state, ambient
temperature change < 0.3 K/min)
Basic error limit (operational limit at 25°C with
a static, thermal state, ambient temperature
change < 0.3 K/min)
3
Voltage
Thermocouple
For measuring voltage
Suppression of interference, limits of error
)
min. 90 dB
SS
min. 70 dB
Min. -50 dB
± 0,1 %
± 1.5 K
± 7 K
± 0,05 %
± 1 K
1
± 5 K
± 0.005 %/K
± 0,01 %
± 0,05 %
± 2.5 K
2
± 1.5 K
Data for selecting a sensor
± 80m V/min. 1 MΩ
Type E, N, J, K, L, S, R, B, T, C/min. 1 MΩ
± 20 V, continuous
Supported
Yes, can be assigned parameters for type E, N,
J, K, L, S, R, B, T, C as per IEC 584
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01