CHAPTER 5: SETTINGS
The C60 contains protection elements for ground time overcurrent (ANSI device 51G) and ground instantaneous
overcurrent (ANSI device 50G). A maximum of six ground time overcurrent and eight ground instantaneous overcurrent
elements are available, dependent on the CT/VT modules ordered with the relay. The following table has details.
CT/VT modules
Slot F
Slot M
8F/8G
8F/8G
8H/8J
8H/8J
8F/8G
8H/8J
5.7.5.2 Ground time overcurrent (ANSI 51G, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  GROUND CURRENT  GROUND TOC1(6)
 GROUND TOC1
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
 GROUND TOC6
 GROUND IOC1
 GROUND IOC2
 GROUND IOC3
 GROUND IOC4
 GROUND IOC5
 GROUND IOC6
 GROUND IOC7
 GROUND IOC8
Ground current elements
Time overcurrent
Instantaneous
overcurrent
4
4
6
6
6
6
6
8
GROUND TOC1
FUNCTION: Disabled
GROUND TOC1 SIGNAL
SOURCE: SRC 1
GROUND TOC1
INPUT: Phasor
GROUND TOC1
PICKUP: 1.000 pu
GROUND TOC1
CURVE: IEEE Mod Inv
GROUND TOC1
TD MULTIPLIER: 1.00
GROUND TOC1
RESET: Instantaneous
GROUND TOC1 BLOCK:
Off
GROUPED ELEMENTS
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
See page 5-192
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Note:
Seen only if slot F or slot M has an 8H or 8J CT
module installed
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
Range: see the Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic operand
5
5-191