1 Introduction
2 Implemented IntOp TISSUES
A–48
This section contains the TISSUES (Technical Issues) Implementation Conformance
Statement (TICS) for the IEC 61850 interface in the 3 Series Family of protective relays.
Date: January 3, 2017
Version 1.10
This tissues conformance statement is applicable to the 3 Series family with firmware
version 2.30.
During the October 2006 meeting IEC TC57 working group 10 decided that:
green Tissues with the category "IntOp" are mandatory for IEC 61850 edition 1
Tissues with the category "Ed.2" Tissues should not be implemented.
Mandatory Edition 1 Tissues
The following table gives an overview of the implemented mandatory Tissues.
Part
Tissue
Description
Nr
8-1
116
GetNameList with empty response?
165
Improper Error Response for GetDataSetValues
183
GetNameList error handling
226
Control negative response (SBOns) with LastApplError
545
Skip file directories with no files
7-4
252
AlmThm should have CDC SPS
7-3
28
Definition of APC
54
Point def xVal, not cVal
55
Ineut = Ires ?
63
mag in CDC CMV
65
Deadband calculation of a Vector and trigger option
219
operTm in ACT
270
WYE and DEL rms values
1199
BCR
7-2
30
control parameter T
31
Typo
32
Typo in syntax
35
Typo Syntax Control time
36
Syntax parameter DSet-Ref missing
37
Syntax GOOSE "T" type
39
Add DstAddr to GoCB
40
GOOSE Message "AppID" to "GoID
41
GsCB "AppID" to "GsID
42
SV timestamp: "EntryTime" to "TimeStamp
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Implemented
Y/na
Y
Y
Y
na
na
na
na
na
Y
Y
Y
na
na
na
na
na
na
na
na
Y
Y
"Y
"na
"na