Integrated power sections: 3-axis CCU box

Description
With the SINUMERIK 810D, three integrated power sections are mounted in the
3-axis CCU box on a heatsink:
S
S
S
Table 4-17
Note
On the integrated power section, the spindle must only be used at "A1".
Current reduction
All technical data are valid for ambient temperatures up to max. 40_C. In the
depending on
event of ambient temperatures > 40_C currents must be reduced linearly as for
the OI mains supply. At a maximum ambient temperature of 55_C: current
ambient
reduction to 60% of the 40_C value.
temperature
Current reduction
All the specified load currents are valid up to a site altitude of 1000m. For site
depending on site
altitudes > 1000m, load currents must be reduced in accordance with the OI
mains supply chart.
altitude
Rated load cycles
For use as an FSD power section (A1--A3)
FSD
Fig. 4-13
E Siemens AG, 2002. All rights reserved
SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition
4.4 Integrated power sections: 3-axis CCU box
Power section for 2x 6A/12A (FDD)
Power section for 1x 18A/36A (FDD) or 24A/32A (MSD)
Heatsink temperature sensor.
Motor connection and power module assignments
Motor
Power section
connection
A1 (back)
18A/36A (FDD) or 24A/32A /MSD)
A2 (center)
6A/12A (as FDD only)
A3 (front)
6A/12A (as FDD only)
I
I
max
I
n
I
= peak current
max
I
= rated current
n
Peak current load cycle with previous load at FSD
4 Description of the SINUMERIK 810D
Continuous current, rated
current (sine, rms)
24O
0.2s
10 s
6O
6O
t
4-77