Commissioning The "Sh" And "Sbc" Functions; General Information About Commissioning Safety Functions - Siemens SINAMICS S120 Installation And Start-Up Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

SINAMICS Safety Integrated (Booksize)

Commissioning the "SH" and "SBC" functions

5.4
Commissioning the "SH" and "SBC" functions
5.4.1

General information about commissioning safety functions

Commissioning notes
Caution
!
For safety reasons, Safety Integrated must be commissioned using STARTER in
online mode.
Reason:
STARTER should only be used to store the safety parameters of a project
monitoring channel. As a result, downloading a project with active Safety
Integrated results in safety problems.
What to do if you download a project when Safety Integrated is active:
S
Switch to online mode and compare the safety parameters between the two
monitoring channels in safety commissioning mode.
S
Exit safety commissioning mode.
S
Switch the power on.
5-162
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition