Oscillographic Data Storage (Version 1.5 And Greater Tpu2000R Only); Figure 5-58. Momentary Pulse Control Illustrated; Figure 5-59. Waveform Capture Buffer Options - ABB TPU2000 Technical Manual

Modbus/modbus plus/ modbus tcp/ip automation
Table of Contents

Advertisement

TPU2000/2000R Modbus/Modbus Plus/ Modbus TCP/IP Automation Guide
Control is processed in that Registers 41456 and 41457 are "ANDED" together. If the resultant logical operation
is completed with the result being a "1" in that bit location, the control function is executed.
TPU2000/TPU2000R offers immediate control. No buffering of commands is attempted.

Oscillographic Data Storage (Version 1.5 and Greater TPU2000R Only)

The TPU2000R has the capability of accepting an option of OSCILLOGRAPHICS (Part Number 588 XXXXX –
X1XXX [X = Don't Care]). The total storage buffer capacity for the TPU2000R is 64 cycles of waveform data,
which consists of four input currents (one per phase and neutral), and three input voltages. A user may configure
the TPU2000R to capture a single or multiple events of waveform capture.
capture buffer as depicted in Figure 5-59.
Waveform
Capture
Buffer
Empty
One Event Captured
8 Cycles/Record
Selected in Configuration
One Event Captured
16 Cycles /Record
Selected in Configuration
One Event Captured
32 Cycles /Record
Selected in Configuration
One Event Captured
64 Cycles/Record
Selected in Configuration
Buffer Full.
EXAMPLE Pulse Output 6 for a momentary time duration as determined Breaker
Failed To Trip time duration.
STEP 1 -
Host sends following register contents
to initiate Physical Output 6 Momentary Pulse
( Assumed that default
password of all spaces is active).
41453 = 2020 hex (Password Hi)
41454 = 2020 hex (Password Lo)
41455 = 0
(Reserved)
41456 = 0040 hex (Select Bit to Pulse)
41457 = 0040 hex ( Confirmation Copy of Register 41200).
E C
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
E C
The Relay Responds over the network that
the command has been accepted.

Figure 5-58. Momentary Pulse Control Illustrated

Cycles
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
7/8 of the buffer available for future event captures
Cycles
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
Cycles
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
Cycles
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
Cycles
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

Figure 5-59. Waveform Capture Buffer Options

STEP 2 -
The host sends the register execute
command to the following address
with the following contents.
41452 = 0001 hex
Command
Sequence Through
Modbus Command 16
Preset Multiple Holding Registers
3/4 of the buffer available for future event captures
1/2 of the buffer available for future
E C
E C
One may think of the waveform
event captures
The
158

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpu2000r

Table of Contents