Siemens OZS164 SERIES WEB SERVER Commissioning Instructions page 24

Table of Contents

Advertisement

LPB / BSB
24 / 108
Siemens
Building Technologies
Path: Home > 0.5 OZS164... > Settings > Communication > LPB / BSB
Data point
D evice number
Default val.:
5
Setting val:
5...8
C lock time source*
Default val.:
Autonomous
Setting val:
Autonomous,
Slave with remote
setting, Slave
without rem
setting, Master
* This setting only works on the LPB. The clock time supplier is assigned
automatically on the BSB.
Web server
Commissioning
Explanation, example
Set the Device number. The device number
(segment and device number) must be
unique within the same LPB bus system.
The setting is meaningless on the BSB: The
BSB device address of the web server is
c
anned (50).
Autonomous: Time/date is created from the
Quartz of the web server. No synchronization
with bus devices.
Slave with remote setting: Web server
receives time/date from master. The master
supplies both date and time on the web
server and is then sent to all bus devices.
Slave without rem setting: Web server
receives time/date from master. The web
server date/time setting is not sent to the
master. The master resets date/time.
Master: Time/date is created from the Quartz
of the web server. The web server supplies
both date and time to all bus devices.
Recommended: Configure web server as
master and bus device as slave with or
w
ithout remote setting.
CE1C5711en
25.08.2010