8.3.

Air Circulation Mode Operation

• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
Air Circulation Mode Operation Time Diagram
8.4.

Automatic Mode Operation

Standard for Determining Operation Mode
• Indoor fan operates at Lo fan speed for 20 seconds.
• After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
• After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
• Room temperature adjustment.
The following are added to the setting temperature specified as above.
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX2 at indoor
electronic controller.
CS-C75KE CU-C75KE / CS-C95KE CU-C95KE / CS-C125KE CU-C125KE