Mitsubishi Electric PURY-P72 Service Handbook page 182

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode J
(2) Heating only operation
Outdoor unit model
Operation
PURY-P144TSHMU-A
PURY-P72THMU-A
PURY-P72THMU-A
Model name of BC controller
CMB-P108NU-A
Ambient
Indoor
21.1°CI- [70°FI-]
tempera-
DBIWB
ture
Outdoor
8.3°CI6.1°C [47°F/43°F]
No. of connected units
4
Unit
Indoor unit
No. of units in operation
4
Model
-
36/36/36/36
Operating
conditions
Main pipe
5 [16-3/18"]
Piping
Branch pipe
m
10
[32-314"]
[ttl
Total pipe length
45 [147-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
34.1
[75]
[Ibs-oz]
Electric current
A
34.6
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
48
48
LEV open-
Indoor unit
350/350/350/350
Pulse
ing
BC controller (1/213)
110/110/870
High pressure(63HS1)/
2.61/0.69
2.61/0.69
Pressure
Low pressure(63LS)
MPa
[378/100]
[378/100]
BC controller on the liquid side(PS1)/
[psi]
2.54/2.22
Intermediate part(PS3)
[368/321]
Discharge (TH4)
69 [156J
69 [156]
Heat exchanger outlet
0 [32]
0 [32]
(TH6)
Outdoor
Accumulator inlet
1 [34]
1 [34]
Temp. of
unit
each sec-
Accumulator outlet
°C
1 [34J
1 [34J
[oF]
tion
Compressor inlet
1 [34]
1 [34]
Compressor shell bottom
40 [104]
40 [104]
LEV inlet
30 [86J
Indoor unit
Heat exchanger inlet
63 [145]
HWEOB03A