Self-Diagnosis Method - Panasonic WH-SHF09F3E5 Service Manual

Air-to-water heatpump
Hide thumbs Also See for WH-SHF09F3E5:
Table of Contents

Advertisement

16.5

Self-diagnosis Method

16.5.1 Connection Capability Rank Abnormality (H12)
Malfunction Decision Conditions:
During startup operation of heating, the capability rank of indoor checked by the outdoor is used to determine
connection capability rank abnormality.
Malfunction Caused:
1
Wrong model interconnected.
2
Wrong indoor unit or outdoor unit PCB (main) used.
3
Faulty indoor unit or outdoor unit PCB (main).
Abnormality Judgment:
Continue for 90 seconds.
87