14. Installation

14.1 Piping Length & Refrigerant Charge
The maximun allowable level and piping length
[Outdoor Unit]
7.5m
Model
Standard Length
[Outdoor Unit]
A2UC/H146FA0
A2UC/H186FA0
A3UC/H216FA0
A4UC/H306FA0
Refrigerant Charge
Indoor Unit Capacity
(Btu/h)
7k, 9k, 12k
3/8"(9.52mm) 1/4"(6.35mm)
18k, 24k
1/2"(12.7mm) 1/4"(6.35mm)
❋ Extra refrigerant = (Extended length - Rated length) x Additional refrigerant
Max piping length each indoor unit
A, B, C, D
A
7.5m
15m
7.5m
15m
7.5m
15m
7.5m
15m
Pipe Size
Gas
Liquid
It does not matter which unit is higher.
Indoor Unit
A
B
C
D
B
C
15m
-
15m
-
15m
15m
15m
15m
Rated
Max
Additional
Length
Length
Refrigerant
7.5m
15m
30g/m
7.5m
15m
30g/m
7.5m
Max total
piping length
D
-
30m(A+B)
-
30m(A+B)
-
45m(A+B+C)
15m
60m(A+B+C+D)
2004 Product Data