1-4 Field Setting And Monitor Mode List for Outdoor unit

Classification
Push switch onoutdoor
Device and
unit PCB
system
Monitor mode
[ F1 ]
Operation of
each part
Time guard
Refrigerant
cycle data 1
Refrigerant
cycle data 2
ITEM
Setting Mode
CODE No.
00
Connected number of indoor unit
01
Software version of outdoor unit
02
Software version of INV PCB
03
Software version of communication PCB
10
Rotational speed of outdoor unit fan motor
11
Rotational speed of INV compressor
12
Current value of INV compressor
14
Pulse of EEV1
Pulse of EEV2
15
20
Accumulated current time
21
INV compressor accumulated time
[ Cooling ]
22
INV compressor accumulated time
[ Heating ]
Information on Thermistor 1
30
( INV compressor discharge temperature )
32
Information on Thermistor 3
( Outdoor temperature )
Information on Thermistor 4
33
( Suction temperature )
34
Information on Thermistor 5
( Heat-exchanger temperature )
36
Information on Thermistor 7
( Liquid temperature 2 )
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
Information on Thermistor 9
38
( Sub-cool heat-exchanger outlet temperature )
Information on Thermistor 10
39
( INV compressor temperature )
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
The number of the communicating unit is displayed
Software version :
[
] [
It skips when there is no suffix
The rotational speed of the outdoor unit fan motor is displayed
[ rpm ]
The rotational speed of the compressor is displayed
[ rps ]
Current value of INV compressor is displayed
[ A ]
Pulse of EEV1 is displayed
[ pls ]
Pulse of EEV2 is displayed
[ pls ]
Accumulated current time is displayed
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or [°F ]
The value of the Thermistor 3 is displayed
[°C ] or [°F ]
The value of the Thermistor 4 is displayed
[°C ] or [°F ]
The value of the Thermistor 5 is displayed
[°C ] or [°F ]
The value of the Thermistor 7 is displayed
[°C ] or [°F ]
The value of the Thermistor 8 is displayed
[°C ] or [°F ]
The value of the Thermistor 9 is displayed
[°C ] or [°F ]
The value of the Thermistor 10 is displayed
[°C ] or [°F ]
The value of the pressure sensor 1 is displayed
[ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-15
Information contents
] [
] [
] [
] displays by five items