  • Page 1 Security Kilsen KFP-CF Series Operation Manual P/N 501-415103-2-10 • REV 1.0 • ISS 01MAY09...
  • Page 2 Trademarks and patents GE and the GE monogram are trademarks of General Electric Company. CleanMe and the Kilsen KFP-CF Series name and logo are trademarks of GE Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
  • Page 3: Table Of Contents

    Operator controls and indicators 5 Acoustic indicators 7 Summary of status indications 7 Control panel operation 10 Access levels 10 Basic operation 11 Advanced operation 13 Maintenance 17 Fire alarm system maintenance 17 Battery maintenance 18 Product compliance 19 Kilsen KFP-CF Series Operation Manual...
  • Page 4 Kilsen KFP-CF Series Operation Manual...
  • Page 5: Introduction

    The choice of operating mode used depends on your location and the specific regional requirements of your fire alarm system. As there is no visual indication of the active operating mode, your installation or maintenance contractor should provide full details of your configuration. Kilsen KFP-CF Series Operation Manual...
  • Page 6: Sounder And Fire Routing Delays

    Operating mode Sounder delay Fire routing delay Extended fire routing delay EN 54-2 EN 54-2 Evacuation EN 54-2 Scandinavia BS 5839-1 NBN S21-100 NEN 2535 Note: Fire routing is not available on any two-zone control panel. Kilsen KFP-CF Series Operation Manual...
  • Page 7: Control Panel Overview

    9. Expansion I/O Fault/Disabled LED 21. Fire Routing Start and 10. General Disable button and LED Fault/Disable/Test button and LEDs 11. General Test button and LED Note: Two-zone control panels do not include fire routing. Kilsen KFP-CF Series Operation Manual...
  • Page 8: User Interface For Eight-Zone Control Panels

    8. Service Detector LED 20. Fire Routing Delay button and LED 9. Expansion I/O Fault/Disabled LED 21. Fire Routing Start and 10. General Disable button and LED Fault/Disable/Test button and LEDs 11. General Test button and LED Kilsen KFP-CF Series Operation Manual...
  • Page 9: Operator Controls And Indicators

    Yellow Indicates that an installed expansion module has a Fault/Disabled LED fault or is disabled. A flashing LED indicates a fault with an expansion module. A steady LED indicates that an expansion module is disabled. Kilsen KFP-CF Series Operation Manual...
  • Page 10 Fire Routing Start Cancels a previously configured delay and activates button and LED fire routing. A flashing LED indicates that fire routing activates when the configured delay elapses. A steady LED indicates that fire routing is active. Kilsen KFP-CF Series Operation Manual...
  • Page 11: Acoustic Indicators

    • The internal buzzer sounds constantly. Alarms activated by a manual call point always take priority over alarms activated by a detector. If an alarm is activated by both devices, the Fire Alarm LEDs and zone alarm LEDs are steady. Kilsen KFP-CF Series Operation Manual...
  • Page 12 • The general Test and the Sounder Fault/Disable/Test LEDs are steady. • There is no acoustic indicator. A fire routing test is indicated as follows: • The general Test and the Fire Routing Start Fault/Disable/Test LEDs are steady. • There is no acoustic indicator. Kilsen KFP-CF Series Operation Manual...
  • Page 13 • The internal buzzer sounds intermittently. When power is re-established the control panel returns to its former status. Caution: To avoid damage to batteries, we recommended that you disconnect them when the control panel is out of service. Kilsen KFP-CF Series Operation Manual...
  • Page 14: Control Panel Operation

    Three short beeps accompanied by a flashing general Fault LED indicate that an incorrect password was entered. Exiting from access level 2 The control panel automatically exits from access level 2 and reverts to access level 1 after five minutes if no button is pressed. Kilsen KFP-CF Series Operation Manual...
  • Page 15: Basic Operation

    (fire routing is activated when the configured delay elapses or when the delay is cancelled). A fire alarm activated by a manual call point overrides any configured delay and activates fire routing immediately. Kilsen KFP-CF Series Operation Manual...
  • Page 16 • The internal buzzer sounds constantly. The test continues for as long as the Test button remains pressed (with an automatic timeout of twelve seconds). When the test is completed the control panel returns to its former state. Kilsen KFP-CF Series Operation Manual...
  • Page 17: Advanced Operation

    Note: Availability of this feature is subject to configuration and its functionality may vary for each zone. Contact your fire system installation or maintenance contractor to confirm your configuration details. Kilsen KFP-CF Series Operation Manual...
  • Page 18 A disabled zone is indicated as follows: • The general Disable LED is steady. • The zone Fault/Disable/Test LED is steady. To enable the zone, press the general Disable button, and then press the Zone button again. Kilsen KFP-CF Series Operation Manual...
  • Page 19 • The Fire Routing Start LED flashes and the test signal (three seconds on/five seconds off) is activated without any configured delay for the duration of the test. To end the test, press the general Test button, and then press the Fire Routing Start button again. Kilsen KFP-CF Series Operation Manual...
  • Page 20 • The Expansion I/O Fault/Disabled LED is steady. To enable the expansion modules, press the general Disable button, and then press Enter again. WARNING: Disabled expansion modules do not indicate a fault or operate if there is a fire alarm. Kilsen KFP-CF Series Operation Manual...
  • Page 21: Maintenance

    Keep the outside and inside of the control panel clean. Carry out periodic cleaning using a damp cloth for the outside. Do not use products containing solvents to clean the unit. Do not clean the inside of the cabinet with liquid products. Kilsen KFP-CF Series Operation Manual...
  • Page 22: Battery Maintenance

    1. Disconnect and remove the existing batteries from the cabinet. 2. Install and connect the replacement batteries using the bridge provided. Observe correct polarity. 3. Dispose of the batteries as required by local or regional regulations. Kilsen KFP-CF Series Operation Manual...
  • Page 23: Product Compliance

    European standards for electrical safety and electromagnetic compatibility These control panels have been designed in accordance with the following European standards for electrical safety and electromagnetic compatibility: • EN 60950-1 • EN 50130-4 • EN 61000-6-3 • EN 61000-3-2 • EN 61000-3-3 Kilsen KFP-CF Series Operation Manual...