Circuit Protectors; Table 1.13 Required Conditions For Distribution Board Circuit Protectors - Fujitsu ETERNUS DX500 S3 Site Planning Manual

Disk storage system
Hide thumbs Also See for ETERNUS DX500 S3:
Table of Contents

Advertisement

Chapter 1
ETERNUS DX Installation
1.7
Outlet/Socket Specifications
1.7.3

Circuit Protectors

Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS
DX or power distribution units to protect the ETERNUS DX by blocking the failed circuit immediately when a
power supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking characteris-
tics.
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.

Table 1.13 Required Conditions for Distribution Board Circuit Protectors

Connected device
Power distribution unit (AC200-240V, 1U, 4 outlets)
Power distribution unit (AC200-240V, 2U, 12 outlets) AC 200 – 240V
Power distribution unit (AC200-240V, 2U, 16 outlets) AC 200 – 240V
ETERNUS DX (without power distribution units)
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Power supply voltage
AC 200 – 240V
AC 100 – 120V
AC 200 – 240V
31
Copyright 2014 FUJITSU LIMITED
Current capacity
Regions other than
EMEA&I region
EMEA&I
15A
20A
30A
15A
16A
P3AM-7712-05ENZ0