2 IN. PER FT
2 IN. PER FT
NOTES:
• Slope hose up in direction of steam flow at 2 in. per foot;
• Slope hose down in direction of steam flow at 3/4 in. per foot;
• Maximum length of remote steam hose is 20 ft.
• Height of P-traps must be greater than the duct static pressure. (Typical 3 in.
will suffice.)
• Minimize sharp bends and elbows.
• Insulating the remote hose in unconditioned spaces will sustain efficiency better
than not insulating the hose.
22
20 FT MAX
GENTLE BEND
10 FT MAX
OBSTRUCTION
SUPPORTED REMOTE HOSE
20 FT MAX
WITH TRAP
P - TRAP
DRAIN
TYPICAL INSTALLATION
WHEN STEAM HUMIDIFIER
IS ABOVE REMOTE NOZZLE
2 IN. PER FT
P - TRAP
DRAIN
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
5 FT MAX
IF NO SLOPE
IF NO SLOPE
2 IN. PER FT
DRAIN
DRAIN
P - TRAP
P - TRAP
M24915A
Steam Humidifier System 69-2285—09