9.4.3 Countermeasure in the event of refrigerant leakage

The facility must have the following features in case of a refrigerant leakage occurs:
1 Provide a shutterless opening which will allow fresh air to circulate into the room.
2 Provide a doorless opening of 0.15% or more size to the floor area.
3 There must be a ventilator fan connected to a gas leak detector, with a ventilator capacity of 0.4 m³/min or higher per 
Japanese refrigeration ton (= compressor displacement volume / 5.7 m³/h) of the air conditioning system using the
refrigerant.
4 Pay special attention to the place, such as a basement, etc., where the refrigerant can stay, since refrigerant is heavier
than air.