Connect the cable

Connect the cable to the unit by connecting the wires to the terminals on the control board
individually according to the unit connection.
The earth wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the wiring diagram behind the panel front of Unit.
CAUTION:
• The diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
CAUTION: The power cord connected to the unit should be complied with the
following specifications.
Model
AKWW0603UA0
AKWW0483UA0
AKWW0363UA0
Allowable temperature to the wire rated at least 90C°
RECOMMAND: Provide a circuit
breaker between power source
and the unit as shown below.
RECOMMAND: The power cord connected to the unit should be complied with
the following specifications (ETL recognized and CSA certified).
The power connecting cable connected to the indoor and outdoor unit should be
complied with the following specifications (ETL recognized and CSA certified).
Low voltage (below 40V)
RECOMMAND: When using the separate wire as the power cord, please fix the
separate wire into the control box panel by using tie wrap as the fixture.
Min.Thickness
(inch
Main/Earth
0.020/0.020
0.013/0.013
0.008/0.008
Line voltage (208~230V)
2
)
Circuit breaker
(NFB)
AWG
6
45A
8
35A
10
30A
Main power source
Air
Conditioner
AWG18
Installation
Leak current circuit breaker
(ELB)
45A 100mA 0.1sec
35A 100mA 0.1sec
30A 100mA 0.1sec
Circuit Breaker
Use a circuit breaker
or time delay fuse.
Installation Manual 25