Changing from Local Control to
To enable external control by an external switch or PLC, follow the
procedure below.
(1) Enabling external control for start/stop and forward/reverse
(To change parameter P08 from "0" to "2")
[Changing procedure]
STOP
Press the STOP button to stop the inverter.
MODE
Press the MODE button three times.
•・•
Change from P01 to P08 using the ••
buttons.
SET
Press the SET button.
•・•
Change from "0" to "2" using the ••
buttons.
SET
Press the SET button and set the data.
∗
This completes setting the data.
(2) Enabling external control for frequency setting signals
(0 to 10V)
(To change parameter P09 from "0" to "4".)
SET
Press the SET button.
•・•
Change from "0" to "4" using the ••
buttons.
SET
Press the SET button and set the data.
MODE
Press the MODE button.
∗
Operation can be started when the data has been set.
<<Potentiometer: P09=2>>
1
10kΩ,
2
1/4W
(Min)
3
65
External Control
....................(Parameter P09)
<<0 to 5V: P09=3>>
<<4 to 20mA: P09=5>>
+
2
2
0 to 5V
200Ω
-
3
3
.......................(Parameter P08)
[Terminal connection (P08=2)]
Main display
3
0
0
0
5
P
0
1
6
P
0
8
<<When P08 = 3, 5>>
0
3
2
5
P
0
9
6
0
[Terminal connection (P09=4)]
4
2
P
1
0
3
0
0
0
(Important)
When using the 4 to 20mA
+
signal, always connect a "200Ω
resistor". The inverter could be
4 to 20mA
damaged if the 200Ω resistor is
not connected.
-
Common termional
ON : Start
OFF : Stop
ON : Reverse
OFF : Forward
Common termional
ON
: Forward run
OFF : Stop
ON
: Reverse run
OFF : Stop
+
0 to 10V
-