Please read these instructions carefully before starting the installation.
This equipment should only be installed by suitably trained operatives.
In all cases ensure safe working practice: Observe precautions for persons in the vicinity of the works.
Ensure that all local, national and international regulations are satisfied.
Check that the electrical specifications of the unit meet the requirements of the site.
Carefully unpack the equipment, check for damage or shortages. Please report any damage immediately.
These units comply with EU Directives:
73/23/EEC (Low Voltage Directive), 89/336/EEC (Electromagnetic Compatibility) and 97/23/EC (Pressure Equipment
Directive). Accordingly, they are designated for use in commercial and industrial environments*.

Avoid installation in the following locations:

Where there is danger of flammable gas leakages.
Where there are high concentrations of oil.
Where the atmosphere contains an excess of salt (as in coastal areas). The air conditioner is prone to failure when
used under this condition unless special maintenance is provided.
Where the airflow from the outdoor unit may cause annoyance.
Where the operating noise of the outdoor unit may cause annoyance.
Where the foundation is not strong enough to fully withstand the weight of the outdoor unit.
Where the water drainage may cause a nuisance or a hazard when frozen.
Where strong winds may blow against the air outlet of the outdoor unit.

Precautions for R407C outdoor units

R407C outdoor units use synthetic oils which are extremely hygroscopic. Therefore ensure that the refrigerant system
is NEVER exposed to air or any form of moisture.
Mineral oils are unsuitable for use in these units and may lead to premature system failure.
Use only equipment which is suitable for use with R407C. Never use equipment which has been used with R22.
R407C should only be charged from the service cylinder in the liquid phase. It is advisable to use a gauge manifold set
equipped with a liquid sight glass fitted in the centre (entry) port.
*
97/23/EC
Pressure Equipment Directive information
Conformity assessment procedure: Module D1
Pressure equipment:
Compressor, category II, Module A1
Accumulator, category I
Liquid receiver, category II
High pressure switch, category II, Module A1
Notified body for inspection and quality assurance systems: BSI, Maylands Avenue, Hemel Hempstead, WP2 4SQ, UK.