Introduction
This is the GE Smart Card Reader Installation Instructions for
models AL-1191 and AL-1193. The smart card reader is a multi-
function, all-purpose proximity card reader suitable for all loca-
tions (including outdoors) that require a short-range reader. You
can connect the reader directly to the Alliance system RS485
databus.
You can configure the reader through the control panel menu
when it is connected to the system databus, through the DGP
menu when it is connected to the local databus, or you can use a
configuration card. Refer to the Smart Card Reader Program-
ming Manual for more information.
The AL-1191 model is shipped with a white removable cover
(there are five other colors available).
Reader components
Figure 1 shows the reader components.
Figure 1. Reader components
AL-1191
AL-1193
Blue LED. Door open, disarmed.
Red LED. Door open, armed
Comms. LED control, buzzer control, power.
Smart Card Reader • AL-1191, AL-1193
Installation Instructions
Installation
You should program the reader and change the default address
(16) before you install the reader. Refer to the Smart Card
Reader Programming Manual for programming details.
You can mount the reader on any flat surface with two #6 (3 to
3.5 mm diameter) panhead screws (Figure 1). We do not recom-
mend using countersunk screws.
You will experience a slightly reduced range if you mount the
reader on a metal surface. If you mount the AL-1191 reader
outdoors, ensure that the blue LED is at the top.
To mount the reader, do the following:
1.
Gently pry the AL-1191 cover sides away from the main
reader body to remove cover and expose the mounting
screws. Do not use excessive force or the reader can be
irreparably damaged.
2.
Mount the reader using the mounting screws.
3.
Gently press the cover over the main body of the AL-1191
reader until it locks into place.
Wiring
Table 1 describes the reader wiring components.
Cover
Table 1.
Wiring components
Wire color
Name
Red
Black
0 V
Green
D-/D0/Data
Blue LED
White
D+/D1/Clock
Brown
LED 1
Red LED
Comms
Yellow
LED 2
Blue LED
Red LED
Blue
Buzzer
Comms
Violet
Open collector
470 ohm
resistor
1040736C • February 2007
Copyright © 2007, GE Security Inc.
Description
Positive 9 to 14 VDC supply.
DC supply ground.
RS485 Data -, Wiegand Data 0
Absolute maximum, 12 V at 10 mA
RS485 Data +, Wiegand Data 1
Absolute maximum, 12 V at 10 mA
Offline LED control configured to two-wire
control will control the red LED only.
Wire grounded: red LED on
Wire open: red LED off
Wire at +5 to +12 V: red LED off
Offline LED Control configured to one-wire
control will control both the red and blue LEDs
Wire grounded: blue LED on
Wire open circuit: both LEDs off.
Wire at +5 V to +12 V: red LED on.
Absolute maximum, 14 V
Configurable to control the blue LED when
offline.
Wire grounded: blue LED on.
Wire open: blue LED off.
Wire at +5V to +12V: blue LED off.
Request-to-exit input when online to Alliance.
This input may be connected to a push button
connected to ground with RTE only selected on
the option card or in Menu 10. Refer to the
Smart Card Reader Programming Manual.
Offline buzzer control.
Wire open or +5V to +12V: buzzer off.
Wire grounded: buzzer sounding.
Absolute maximum, 14 V.
Configurable as: door relay, tamper output,
credit controlled pulse, timed, or latched
output.
Absolute maximum, 14 V at 25 mA
This is a low current output and must not be
used to directly energize high current door
openers.
Used to terminate RS485 bus when the reader
is the last device on the bus.
Install across D+ (white) and D- (green).

Advertisement

loading

Summary of Contents for GE AL-1191

  • Page 1 This is the GE Smart Card Reader Installation Instructions for You should program the reader and change the default address models AL-1191 and AL-1193. The smart card reader is a multi- (16) before you install the reader. Refer to the Smart Card function, all-purpose proximity card reader suitable for all loca- Reader Programming Manual for programming details.
  • Page 2 Controller DGP local bus with a request-to-exit input. Figure 2. System bus connections Figure 4. Local bus connections Control panel J8 to J12 Green White Violet Black +12V AL-1191/AL-1193 System bus Green AL-1191/AL-1193 White Black +12V Violet (open collector) Green White Black...
  • Page 3: Specifications

    FCC compliance Specifications This device complies with part 15 of the FCC rules. Operation is subject to the Current consumption following conditions: Standby 25 mA 1. This device may not cause harmful interference. Active 80 mA maximum 2. This device must accept any interference received, including interference Input voltage 9 to 14 VDC that may cause undesired operation.

This manual is also suitable for:

Al-1193