Basic Operation
continued
occurs, the UPS will normally switch to providing PWM sine wave
power from its battery reserves for as long as the distortion is present.
In areas with poor utility power or where the UPS's input power comes
from a backup generator, chronic waveform distortion could cause the
UPS to switch to battery too frequently, draining its battery reserves. You
may be able to reduce how often your UPS switches to battery due to wave
form distortion by experimenting with different settings for this dial. As
the dial is turned clockwise, the UPS becomes more tolerant of vari-
ations in its input power's AC waveform. NOTE: The further the dial is
adjusted clockwise, the greater the degree of waveform distortion the
UPS will allow to pass to connected equipment. When experimenting
with different settings for this dial, operate connected equipment in a
safe test mode so that the effect on the equipment of any waveform
distortions in the UPS's output can be evaluated without disrupting
critical operations.
Storage & Service
Storage
CAUTION! Your UPS has an internal power source. Its outlets may still deliver current, even
after the UPS is unplugged, until the UPS is completely turned OFF (deactivated). Before stor-
ing your UPS, turn it completely OFF: with the UPS ON and receiving utility power, press and
hold the POWER button for one second (an alarm will beep once briefly after the interval has
passed); then, unplug the UPS from the wall outlet. If you store your UPS for an extended peri-
od of time, recharge the UPS batteries once every three months: plug the UPS into a wall out-
let; allow it to charge for 4 to 6 hours; and then unplug it and place it back in storage. Note:
after you plug the UPS in, it will automatically begin charging its batteries; however, it will not
supply power to its outlets (see Quick Installation section). If you leave your UPS batteries dis-
charged for an extended period of time, they will suffer a permanent loss of capacity.
Service
Before returning your UPS for service, follow these steps:
1. Review the installation and operation instructions in this manual to ensure that the service
problem does not originate from a misreading of the instructions. Also, check that the UPS
System's circuit breaker(s) are not tripped. This is the most common cause of service inquiries
which can be easily remedied by following the resetting instructions in this manual.
2. If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp
Lite at (773) 869-1233. A service technician will ask for the UPS's model number, serial num-
ber and purchase date and will attempt to correct the problem over the phone.
3. If the problem requires service, the technician will issue you a Returned Material
Authorization (RMA) number, which is required for service. If you require packaging, the tech-
nician can arrange to send you proper packaging. Securely pack the UPS to avoid damage dur-
ing shipping. Do not use Styrofoam beads for packaging. Any damages (direct, indirect, spe-
cial, incidental or consequential) to the UPS incurred during shipment to Tripp Lite or an autho-
rized Tripp Lite service center is not covered under warranty. UPS Systems shipped to Tripp
Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark
the RMA number on the outside of the package. If the UPS System is within the 2-year war-
ranty period, enclose a copy of your sales receipt. Return the UPS for service using an insured
carrier to the address given to you by the Tripp Lite service technician.
8

Specifications

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
SmartPro
®
UPS Systems
Model Number:
SMART700
Series Number:
AGSM700PJR3
Input Voltage/Frequency:
120V/60 Hz
On-Line Input Voltage Range:
79 - 147 volts
Output Capacity (VA/Watts):
700/450
Battery Runtime
(Half Load/Full Load) Minutes:
20/6
Battery Recharge Time:
2-4 hrs.
Approvals:
UL, cUL, NOM, FCC B
SmartPro
®
XL UPS Systems
Model Number:
SMART750XL
Series Number:
AGSM1500XPSR3
Input Voltage/Frequency:
120V/60 Hz
On-Line Input Voltage Range:
79 - 147 volts
Output Capacity (VA/Watts):
750/600
Battery Runtime
(Half Load/Full Load) Minutes:
29/12+
Battery Recharge Time:
2 - 4 hrs.
Approvals:
UL, cUL, NOM, FCC A
ALL UNITS:
Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression
(exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB at 1MHz); AC Protection Modes (H to N, H to G, N to G).
+ Battery runtime can be extended with addition of optional Tripp Lite External Battery Packs (Model #: BP36V27, sold separate-
ly). External batteries will increase both the battery runtime and the battery recharge time.
FCC RADIO/TV INTERFERENCE NOTICE (U.S. ONLY):
This device complies with part 15 of the FCC Rules.Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause unde-
sired operation.
FCC CLASS A RADIO/TV INTERFERENCE NOTICE (U.S. ONLY):
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when operated in a com-
mercial environment. This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in
accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must
use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the
party responsible for compliance could void the user's authority to operate the equipment.
FCC CLASS B RADIO/TV INTERFERENCE NOTICE (U.S. ONLY):
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy, and if not installed and used in accordance with the
instruction manual, may cause interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference using one or more of the
following measures: reorient or relocate the receiving antenna; increase the separation between the equipment and the receiver;
connect the equipment into an outlet on a circuit different from that which the receiver is connected; consult the dealer or an expe-
rienced radio/television technician for help. The user must use shielded cables and connectors with this product. Any changes or
modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to
operate the equipment.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V : DC Voltage
SMART1050
SMART1500
AGSM1050PJR3
AGSM1500XPSR3
120V/60 Hz
120V/60 Hz
79 - 147 volts
79 - 147 volts
1050/705
1500/980
23/8
20/7
2-4 hrs.
2-4 hrs.
UL, cUL, NOM, FCC B
UL, cUL, NOM, FCC A
SMART1050XL
SMART1500XL
AGSM1500XPSR3
AGSM1500XPSR3
120V/60 Hz
120V/60 Hz
79 - 147 volts
79 - 147 volts
1050/800
1500/980
19/8+
20/7+
2 - 4 hrs.
2 - 4 hrs.
UL, cUL, NOM, FCC A
UL, cUL, NOM, FCC A