Honeywell Q682 User Manual page 16

Heating or cooling thermostat and wallplate or heating/cooling thermostat and subbase
Hide thumbs Also See for Q682:
Table of Contents

Advertisement

Troubleshooting (Continued)
Problem
Room
temperatures
are not correct
(continued).
Burner-on time
too short.
Burner-on time too
long.
Check
— Thermostat circuits.
— Anticipator setting. (See Fig. 6
for anticipator location.)
— Anticipator setting. (See Fig. 6
for anticipator location.)
Action
Heating mode—Move temperature
setting levers 5° F [3° C] above room
temperature. Heating system should
start.
Cooling mode—Move temperature
setting levers 5° F [3° C] below room
temperature. Cooling system should
start. If the system does not operate,
call a qualified service technician.
Increase anticipator setting by 0.05
(e.g., 0.4 to 0.45). Observe burner
operation.
Decrease anticipator setting by 0.05
(e.g., 0.45 to 0.4). Observe burner
operation.
16
(continued)
69-0643—1