Honeywell DMULTISTAGE T8524C Installation Instructions Manual page 5

Multistage microelectronic thermostats
Table of Contents

Advertisement

Installer Setup
Number
(Press i key
to change)
Select
Not used
01
a
Fan operation
02
Not used
03 and 04
Stage-two
05
heating cycle
rate
Not used
06 thru 11
Changeover
12
(T8524D only)
Not used
13
Degree
14
temperature
display
Not used
15 thru 18
Extended fan
19
operation in
a,b
heating
Extended fan
20
operation in
a
cooling
Not used
21 thru 23
Outdoor
24
temperature
a
display
Not used
25 thru 29
Deadband
30
Not used
31 and 32
Minimum off
33
time for the
compressor
a
Available on select models.
b
Installer Setup Number 02 must be set to 01 to extend fan operation.
T8524C,D MULTISTAGE MICROELECTRONIC THERMOSTATS
Table 2. Thermostat Installer Setup Options.
Factory-Setting
Display
Description
00
Conventional applica-
tions where equipment
controls fan operation in
heat mode
06
6 cph used for
conventional systems
01
Manual changeover
00
Temperature is
displayed in °F
00
No extended fan
operation after the call
for heat ends
00
No extended fan
operation after the call
for cool ends
00
No outdoor temperature
is displayed
03
Heating and cooling
setpoints can be set no
closer than 3°F (1.5°C)
05
5 minute minimum off
time for the compressor
Other Choices
(Press
Display
01
Heat pump and electric heat
applications where
thermostat controls fan
operation in heat mode
01, 03,
01—1 cph used for radiant
or 09
floor heat, gravity systems
03—3 cph used for hot water
systems or high efficiency
furnaces
09—9 cph used for electric
heat systems
00
Automatic changeover
01
Temperature is displayed in
°C
01
Fan operation is extended
90 seconds after the call for
heat ends
01
Fan operation is extended
90 seconds after the call for
cool ends
01
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate.
04 thru
Heating and cooling
10
setpoints can be set no
closer than the chosen
value:
04—4°F (2°C)
05—5°F (2.5°C)
06—6°F (3°C)
07—7°F (3.5°C)
08—8°F (4°C)
09—9°F (4.5°C)
10—10°F (5°C)
00, 01,
Minimum number of minutes
02, 03
(0 thru 5) the compressor will
or 04
be off between calls for the
compressor
5
or
key to change)
Description
Actual
Setting
(Continued)
69-1055-1