Technical Specifications - HP ProLiant DL360 Generation 7 (G7) Quickspecs

1u server
Table of Contents

Advertisement

QuickSpecs

Technical Specifications

System Unit
Dimensions (H x W x D)
(with bezel)
Weight
(approximate)
Input Requirements
(for Standard 460W PSU,
see power specifications
tables for detail on 460W,
750W and 1200W power
supplies)
BTU Rating
Power Specifications
Power Supply Output
(per power supply)
System Inlet
Temperature
Relative Humidity
(non-condensing)
DA - 13598 North America — Version 56 — March 25, 2013
HP ProLiant DL360 Generation 7 (G7)
1.70 x 16.78 x 27.25 in (4.32 x 42.62 x 69.22 cm)
Maximum
(all hard drives, power
supplies, and processors
installed)
Minimum
(one hard drive, power
supply, and processor
installed)
Rated Line Voltage
Rated Input Current
Rated Input Frequency
Maximum
To review typical system power ratings use the HP Power Advisor which is
available via the online tool located at URL:
efficient
or
www.hp.com/go/hppoweradvisor
- Click on the system of interest. Example: DL360 G7
- Follow the instructions of the next screens.
Rated Steady-State Power 460 W (at 100 VAC),
Maximum Peak Power
Operating
Non-operating
Operating
Non-operating
39.5 lb (17.92 kg)
32 lb (14.51 kg)
100 to 240 VAC
4.5 Amps (at 120VAC) to 2.2 Amps (at 240 VAC)
50 to 60 Hz
1773 BTU / hr (at 120 VAC), 1715 (at 240 VAC)
www.hp.com/go/proliant-energy-
460 W (at 200 VAC)
460 W (at 100 VAC),
460 W (at 200 VAC)
NOTE: See Power Supply Specifications tables for
complete details on 460W PSU and optional 750W
and 1200W Power Supply Options.
10° to 35° C (50° to 95° F) at sea level with an
altitude derating of 1.0°C per every 305 m (1.8° F
per every 1000 ft) above sea level to a maximum
of 3050 m (10,000 ft), no direct sustained
sunlight. Maximum rate of change is 10° C/hr (18°
F/hr). The upper limit may be limited by the type
and number of options installed.
System performance may be reduced if operating
with a fan fault or above 30° C (86° F).
-30° to 60° C (-22° to 140° F). Maximum rate of
change is 20° C/hr (36° F/hr).
10 to 90% relative humidity (Rh), 28° C (82.4° F)
maximum wet bulb temperature, non-
condensing.
5 to 95% relative humidity (Rh), 38.7° C (101.7° F)
maximum wet bulb temperature, non-
condensing.