Parameter data record
A.1 Dependencies when configuring with GSD file
Measurement
Measuring range
type
(3-wire
Cu 10 climatic
connection)
Thermal resistor
Pt100
(2, 3, 4-wire
Pt200
connection)
Pt500
Pt1000 standard
Ni100
Ni120
Ni200
Ni500
Ni1000 standard
LG-Ni 1000
standard
Thermal resistor
Cu 10 standard
(3-wire
connection)
Thermocouple
Type B, N, E, R, S,
J, L, T, K, U, C,
TXK
x = property is allowed, – = property is not allowed, * = property is not relevant
Use of "Reference channel of the module":
1
- Channel 0 must be set as "Pt100 climatic" with temperature unit: "Degrees Celsius".
-For each TC channel of this module that is intended to use channel 0 as reference, "Reference junction" must be set to
"Reference channel of the module".
Use of "Reference channel of group 0, 1, 2, 3":
2
- An RTD channel must be set as "Pt100 climatic" with temperature unit: "Degrees Celsius".
- "Reference channel of group 0, 1, 2, 3" must be set as the "Reference junction" of this channel.
- There must only be one RTD channel with "Reference junction" = "Reference channel of group 0, 1, 2, 3" per group 0,
1, 2, 3 and IO device!
- For each TC channel in the IO device that is intended to use this reference, "Reference junction" must be set to
"Reference channel of group 0, 1, 2, 3".
- If the reference channel is on channel 0, it can also be used as "Reference channel of the module" at the same time.
48
Temperature
Reference junction Temperature unit
coefficient
Cu 0.00427
Pt 0.00385055
No reference
Pt 0.003916
channel mode
Pt 0.003902
Pt 0.00392
Pt 0.00385
Ni 0.00618
Ni 0.00672
LG-Ni 0.005
Cu 0.00427
*
Reference channel
of the module
Internal reference
junction
Reference channel
of group 0, 1, 2, 3
Fixed reference
temperature
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Degrees Celsius
Degrees
Fahrenheit
Kelvin
Degrees Celsius
1
Degrees
Fahrenheit
Kelvin
2
Manual, 02/2014, A5E03573289-AD
Conductor
resistance
*
x (with 2-wire
connection)
*
*